EE110
EE110
Twilight switch, daily cycle
Technical properties
Architecture
Fixing mode Din-Rail
Functions
Power reserve ≈ 200 h
Configuration
Number of modules 5
Controls and indicators
Presence button No
Main electrical features
Frequency 50/60 Hz
Voltage
Operating voltage 230 V~ +10%/-15%
Electric current
Acceptable current rating with AC1 16 A
Max. power with cos phi 0.6 10 A
Dimensions
Depth of installed product 65 mm
Height of installed product 85 mm
Width of installed product 88 mm
Width of rail mounted device (RMD) 5 modules
Frequency
Frequency range 50…60 Hz
Power
Fluorescent lamps duo circuit 1000 W
Max. power with fluo uncompensated lamps 1000 VA
Power consumed 1.5 VA
Power consumption (operation) 1.5 VA
Incandescent bulb power 2000 W
Total power loss under IN 1.5 W
Power dissipation per coil 0.3 W
Max. Breaking capacity for parallel
compensated fluorescent tubes 200 W
Subject to technical modifications
Max. Breaking capacity for row-
compensated fluorescent tubes 1000 W
Endurance
Electrical endurance cycles with
incandescent lighting 7500
Electrical durability at nominal load in AC1
in operating cycles 50000
Electrical durability with parallel
compensated fluorescent tubes 4000
Electrical durability with row-compensated
fluorescent tubes 7500
Measurement
Running accuracy ± 6 min/year
Battery
Charging time of the power reserve in hours 70
Power supply
Supply voltage 230 V
Lighting control
Brightness measurement range 5 / 2000 Lux
Fluorescent bulbs control
Max. power with fluorescent parallel lamps 200 VA
Max. power fluo. duo lamp comp. series 1000 W
Fluorescent lamps parallel compensated 200 W
Fluorescent lamps uncompensated 1000 W
Incandescent bulbs control
Max. power with incandescent lamps 2000 W
230 V incandescent lamps 2000 W
230 V halogen lamps 1000 W
Installation, mounting
Mounting type din-Rail
Installation mode for mounting on DIN rail
Connection
Conductor cross-section (flexible) 0.5…4 mm²
Conductor cross-section (rigid) 0.5…4 mm²
Number of contacts 1
Type of contacts 1 changeover
Type of connection with screw terminals
Settings
Delay ON 15 s
Delay OFF 60 s
Shortest switching time 15 mn
Setting Brightness modifiable via potentiometer
Subject to technical modifications
Equipment
Supply failure reserve 200 h
Potential-free with potential-free change-over contact
Use
Cycle daily
Safety
Protection index IP IP20
REACH conform No
RoHS conform No
Halogen free No
Use conditions
Operating temperature -10…50 °C
Working accuracy 6 mn / year
Storage/transport temperature -20…60 °C
Subject to technical modifications

Produkspesifikasjoner

Merke: Hager
Kategori: Bryter
Modell: EE110

Trenger du hjelp?

Hvis du trenger hjelp med Hager EE110 still et spørsmål nedenfor, og andre brukere vil svare deg




Bryter Hager Manualer

Hager

Hager HZC001 Bruksanvisning

13 Desember 2024
Hager

Hager FN091E Bruksanvisning

13 Desember 2024
Hager

Hager VZ118P Bruksanvisning

13 Desember 2024
Hager

Hager VZ418T Bruksanvisning

13 Desember 2024
Hager

Hager VZ318P Bruksanvisning

13 Desember 2024
Hager

Hager VZ118T Bruksanvisning

13 Desember 2024
Hager

Hager VZ218P Bruksanvisning

13 Desember 2024
Hager

Hager VZ318T Bruksanvisning

13 Desember 2024
Hager

Hager VZ418P Bruksanvisning

13 Desember 2024
Hager

Hager KN22E Bruksanvisning

12 Desember 2024

Bryter Manualer

Nyeste Bryter Manualer