Enda ET2411 Bruksanvisning
Les nedenfor 📖 manual på norsk for Enda ET2411 (2 sider) i kategorien Termostat. Denne guiden var nyttig for 4 personer og ble vurdert med 4.5 stjerner i gjennomsnitt av 2 brukere
Side 1/2
ENDA 2411 ON/OFF HEAT CONTROLLER ET
SET
°C
SET
ET2411
ENDA
°F C1
230V AC + % - %, 50/60Hz 24V AC %10 20 or 12/ /DC 10
Max. 3 VA
Power connector : 2.5mm² screw-terminal, Signal connector : 1,5mm² screw-terminal conenction.
EN 61326-1 : 2013 (Performance criterion B is satised for EN 61000-4-3)
EEPROM ( 10 )Min. years
Max. 100ohm
EN 61010-1 : 20 (Pollution degree 2, overvoltage category II) 10
12 bit , sampling time.resolution 100ms
Max. 2000m
Do not use the device in locations subject to corrosive and ammable gasses.
Max. humidity 80% for temperatures up to 31°C decreasing linearly to 50% relative humidity at 40°C.
0 ... +50 / -25... +70
°C °C without icing( )
According to EN60529; Front panel: IP65 Rear panel : IP20
S alc e Range Accuracy
EN 60751
- ... 0 °C -76.0...302.0°F60.0 15 .0
± 1% (for full scale) ± 1 Digit
Supply
HOUSING
Housing Type
Dimensions
Weight
Enclosure Materials
CONTROL
ontrolC Type
Control Algorithm
A/D Converter
Hysteresis
INPUT
Height
Ambient/Storage temperature
Relative Humidity
Protection Class
Input Type
NTC Sensor Typ 103AT-2
at 25 °C - 10 kOhm
77mm
61mm 5mm
2
Connection
Cable Panel Rubber
Packing
71,5mm
1
For 5A Models : 250V AC, 5A (resistive load), NO control output.
For 8A Models : 250V AC, 8A ( ), NO and NC control output.resistive load
For 16A Models : 250V AC, 16A ( ), NO control output.resistive load
For 5A Models : 5. Switching for no-load operation; 100.000 switching for 5A resistive load at 250VAC. Mio.
OUTPUT
Life Expectancy for Relay
C1 Output
Thank you for choosing ON/OFF Heat Controller.ENDA ET2411
Read this document carefully before using this device. The guarantee will be expired by device
demages if you don't attend to the directions in the user manual. Also we don't accept any
compensations for personal injury, material damage or capital disadvantages.
Holding screw
0.4-0.5Nm.
Equipment is protected throughout
by DOUBLE INSULATION
5
6
SUPPLY:
NOTE:
184-253V AC
50/60Hz 3VA
Line
Neutral
230V AC
Supply
Switch
Note:
Cable size: 1,5mm²
Fuse
F 100 mA
250V AC
Fuse should
be connected
1) Mains supply cords shall meet the requirements of
IEC 60227 or IEC 60245.
2) In accordance with the safety regulations, the power
supply switch shall bring the identication of the
relevant instrument and it should be easily
accessible by the operator.
TECHNICAL SPECIFICATIONS
ENVIRONMENTAL CONDITIONS
ELECTRICAL CHARACTERISTICS
Power onsumptionC
Wiring
Indicator
EMC
Safety Requirements
Data Retention
Line Resistance
4 digits, 12.5mm, 7 segment red LED
Single and alarm .-setpoint control
Adjustable between 0.1 and 20.0°C/F.
according to DIN 43 700.Suitable for ush-panel mounting
5 1W77xH3 xD6 mm
Approx. 215g (A )fter packing
Self extinguishing plastics
While cleaning the device, solvents (thinner, benzine, acid etc.) or corrosive materials must not be used.
Dimensions
For removing mounting clamps:
-Push the ush-mounting clamp
in direction as shown in the
gure below.Then,pull
out the clamp in direction .
1
2
Depth
Flush mounting
clamp
Flush mounting
clamp Panel cut-out Note:1) Panel thickness should
be maximum 7mm.
2) If there is no 60mm free
space at the back side of
the device,it would be
dicult to remove it from
the panel.
t
ENDA ET2411 is intended for installation within control panels. Make sure that the device is used only for
intended purpose. The shielding must be grounded on the instrument side. During an installation, all of the
cables that are connected to the device must be free of electrical power. The device must be protected against
inadmissible humidity, vibrations, severe soiling. Make sure that the operation temperature is not exceeded.
All input and output lines that are not connected to the supply network must be laid out as shielded and twisted cables.
These cables should not be close to the power cables or components. The installation and electrical connections must
be carried out by a qualied sta and must be according to the relevant locally applicable regulations.
For 8A Models : 30. Switching for no-load operation; 300.000 switching for 8A resistive load at 250VAC. Mio.
For 16A Models : 30. Switching for no-load operation; 100.000 switching for 16A resistive load at 250VAC. Mio.
ET2411-230-08
DIGITAL THERMOSTAT
250V AC 8A
RESISTIVE LOAD
8 680407 71 5 299
Made in Turkey
C1
1 2 3 4 5 6 7 8 9 10 11 12
NTC
SN: XXXXXXXXX
ENDA INDUSTRIAL ELECTRONICS
ET2411-230-16
DIGITAL THERMOSTAT
250V AC 16A
RESISTIVE LOAD
8 680407 71 5 367
Made in Turkey
C1
1 2 3 4 5 6 7 8 9 10 11 12
NTC
SN: XXXXXXXXX
ENDA INDUSTRIAL ELECTRONICS
ET2411-SM-05
DIGITAL THERMOSTAT
250V AC 5A
RESISTIVE LOAD
8 680407 71 5 350
Made in Turkey
C1
1 2 3 4 5 6 7 8 9 10 11 12
NTC
SN: XXXXXXXXX
ENDA INDUSTRIAL ELECTRONICS
ET2411-230-08
DIGITAL THERMOSTAT
250V AC 8A
RESISTIVE LOAD
680407715299
Made in Turkey
C1
1 2 3 4 5 6 7 8 9 10 11 12
NTC
SN: XXXXXXXXX
ENDA INDUSTRIAL ELECTRONICS
Order Code : ET2411 - -
1 2
1 - Supply Voltage
230... 230V AC
24........24V AC
.....
0 /DC
012........12V AC/DC
SM.........7-24VAC/9-30VDC
2 - Relay Current Selection
05.....5A Re
08.....8A
lay Output
Relay Output
16...16A Relay Output
SET
°C
SET
ET2411
ENDA
°F C1
- 77 x 35mm sized.
- Single NTC sensor input.
- Zero point input shift.
- Selectable heating or cooling control for C1 relay output.
- Upper and lower setpoint limits can be adjusted.
- Temperature unit can be selected as °C or °F.
- CE marked according to European Norms.
- Selectable heating or cooling control.
- In the case of sensor failure, relay state can be set to ON or OFF.
english
SURAN Industrieelektronik
Dettinger Str. 9
D-72160 Horb a.N.
Tel.: +49 (0)7451 / 625 617 E-mail : info@suran-elektronik.de
Fax: +49 (0)7451 / 625 0650 Internet : www.suran-elektronik.de
up to date: 25.03.2019, modication reserved and can be change any time previous notice !
ET2411-E-25032019
1. / 2
R HS
Konform
C1.Hy. = Output hysteresis value.
It can be adjusted between and .0.1 20.0 °C
C.typ. = Control type selection.
C.typ. HEAt
C.typ. CooL
=
=
Heating control is selected.
Cooling control is selected.
Unit = Temperature unit selection.
Unit. °C °F = Can be selected as or
d.P. = Decimal point display selection.
If , decimal value is not dotted.
If = , decimal value is dotted.
d.P.. no
d.P. YES
=
S.Cod = Access code for security menu.
This parameter should be .411
C1..sc. C1,Cn.
nonE
P.yEs
P. no
=
=
= Can be m ed
Visible but can’t be modied
Security menu access level.
Invisible.
odi .
= .
..Co.sc. ConF.
nonE
P.yEs
P. no
=
= Invisible.
= Can be modified.
Visible but can’t be modied.
Conguration menu access level.
=
C.S.sc.
P.yEs
P. no
= security access level.
=
.
C1 set value
Can be modified.
= Visible but can’t be modied
C1..L.L.
C1..H.L.
C1.Hy.
C.tyP.
Unit.
d.P.
C1.Cn. ConF. SECu.
S.Cod.
C1.sc.
Co.sc.
C.S..sc.
SET SET SET
Programming Menu
Default
Value
P.YES
P.YES
P.YES
0
HEAt
°C
no
Programming Diagram
SET
SET
Measured temperature
105 C1.SE.
Running Mode
100
C1 Set value
101 102 101
Default value
100 If no key is pressed within 3 seconds, Running Mode is entered.
oFFS. = Oset .
Zero point shift value is added to the measured
value. This feature is used for eliminating the
measuring probe distance errors. It can be
adjusted between - and °C.
value
20.0 20.0
oFFs.
0
C1.E.S.
on
off
= C1 Output state in case of sensor failure.
= Output is ON in case of sensor failure.
= Output is OFF in case of sensor failure.
C1.E.S.
Entering Running Mode in Programming Mode :
When this button is pressed
message is appeared
and
C.SEt
temperature setpoint
adjustment mode is entered.
C1..L.L.= Control set point lower limit for C1
output.
It can be adjusted between -60.0 and
parameter value.
C1.H.L.
C1H.L.= Control set point upper limit for C1
output.
It can be adjusted between 150.0 and
parameter value.
C1.L.L.
Default
Value
Modication Of Parameter Diagram
Wh holding key, parameter and
using keys the requested value can be adjusted.
ile down value blinks by
,
SET SET SET
SET
ERROR MESSAGES
pfa
____
Sensor is broken
Temperature value is
higher than the scale
Temperature value is
lower than the scale
----
SET
If key is pressed while holding down key,
then Programming Menu is entered.
when one of these buttons are pressed for the rst time, blinking setpoint value appears.
Temperature setpoint value is adjusted with buttons then,
In Programmin Mode, if no keys are pressed for 20 seconds information is
saved automatically and Running Mode is entered.
Alternatively, if and keys are pressed together, Programming Menu
is entered. In the Programming Menu, if key is pressed while holding
down key, then Running Mode is entered.
SET
SET
When , if key is
pressed for 4 seconds while holding
down key, then is seen
on display and the device is returned
to factory settings.
s.co. = 0
d.PAr.
If key is pressed and held 0.6 seconds, the value of the
selected parameter increases rapidly. If waited enough,the
value increases a hundred at each step. After 1 second,
following the release of the key, initial increasing condition is
returned. The same procedure is valid for the decrementing.
ET2411-E-25032019
2. / 2
Produkspesifikasjoner
Merke: | Enda |
Kategori: | Termostat |
Modell: | ET2411 |
Trenger du hjelp?
Hvis du trenger hjelp med Enda ET2411 still et spørsmål nedenfor, og andre brukere vil svare deg
Termostat Enda Manualer
27 Oktober 2024
27 Oktober 2024
27 Oktober 2024
22 Oktober 2024
18 Oktober 2024
18 Oktober 2024
Termostat Manualer
- Termostat ORNO
- Termostat Bosch
- Termostat Boneco
- Termostat Siemens
- Termostat EBERLE
- Termostat Schwaiger
- Termostat AEG
- Termostat TP Link
- Termostat Oreg
- Termostat Netatmo
- Termostat Busch-Jaeger
- Termostat Brennenstuhl
- Termostat Danfoss
- Termostat Somfy
- Termostat Panasonic
- Termostat Schneider
- Termostat EMOS
- Termostat Heatit
- Termostat Dimplex
- Termostat Velleman
- Termostat GE
- Termostat Nexa
- Termostat Nobo
- Termostat Tru Components
- Termostat Bearware
- Termostat Elgato
- Termostat Avidsen
- Termostat STI
- Termostat Hunter
- Termostat Basetech
- Termostat TFA
- Termostat Tesla
- Termostat Renkforce
- Termostat REMKO
- Termostat ATAG
- Termostat Drayton
- Termostat Jung
- Termostat Ambiano
- Termostat Crestron
- Termostat Xavax
- Termostat Techno Line
- Termostat Remeha
- Termostat Heatmiser
- Termostat Wolf
- Termostat GENERAL Life
- Termostat Silvercrest
- Termostat AVM
- Termostat HomePilot
- Termostat Elektrobock
- Termostat Corberó
- Termostat Perel
- Termostat Delta Dore
- Termostat Homematic IP
- Termostat Vimar
- Termostat Emerson
- Termostat Salus
- Termostat Fenix
- Termostat Honeywell
- Termostat Junkers
- Termostat Eliwell
- Termostat Grasslin
- Termostat Jumo
- Termostat Orbis
- Termostat Fantini Cosmi
- Termostat Vemer
- Termostat Qubino
- Termostat Theben
- Termostat EQ3
- Termostat Etherma
- Termostat Saunier Duval
- Termostat Gewiss
- Termostat Viessmann
- Termostat Bticino
- Termostat Conrad
- Termostat Econo-Heat
- Termostat Elro
- Termostat Gira
- Termostat Tado
- Termostat Brink
- Termostat Emmeti
- Termostat Itho
- Termostat Bryant
- Termostat Aube
- Termostat Baxi
- Termostat Seitron
- Termostat Amfra
- Termostat Vaillant
- Termostat Carel
- Termostat Buderus
- Termostat Optima
- Termostat Frico
- Termostat UPM
- Termostat Computherm
- Termostat Veria
- Termostat Innogy
- Termostat Nefit
- Termostat ICY
- Termostat Levica
- Termostat Itho-Daalderop
- Termostat Carrier
- Termostat Radson
- Termostat ChiliTec
- Termostat King
- Termostat ACV
- Termostat Landis Gyr
- Termostat Nest
- Termostat Oventrop
- Termostat IMIT
- Termostat Horstmann
- Termostat ELKO
- Termostat Alecto
- Termostat Google
- Termostat Emko
- Termostat Wachendorff
- Termostat MundoControl
- Termostat Otio
- Termostat Rose LM
- Termostat Tylö
- Termostat Sinustec
- Termostat TrickleStar
- Termostat Finder
- Termostat Sygonix
- Termostat Warmup
- Termostat Plugwise
- Termostat Lowes
- Termostat Go Green
- Termostat Drayton Erie
- Termostat Intertechno
- Termostat EQ-3
- Termostat Johnson Control
- Termostat RWE
- Termostat Webasto
- Termostat Tellur
- Termostat OJ ELECTRONICS
- Termostat Zehnder
- Termostat Plieger
- Termostat HomeMatic
- Termostat Eneco
- Termostat VDH
- Termostat Maico
- Termostat Yokis
- Termostat Eurotronic
- Termostat HQ
- Termostat Ouellet
- Termostat THERMAFLEX
- Termostat Truma
- Termostat Wallair
- Termostat AWB
- Termostat PECO
- Termostat Worcester-Bosch
- Termostat 2Heat
- Termostat EasyTemp
- Termostat Hugo Muller
- Termostat Watts
- Termostat Westfalia
- Termostat Oregon Scientific
- Termostat H-Tronic
- Termostat Z-Wave
- Termostat Easy Timer
- Termostat Fibaro
- Termostat SPC
- Termostat Muller
- Termostat Bulex
- Termostat Helios (Amfra)
- Termostat IR-V
- Termostat Eqiva
- Termostat Hager
- Termostat Energenie
- Termostat Thermy
- Termostat Ferroli
- Termostat Niko
- Termostat Stiebel Eltron
- Termostat De Dietrich
- Termostat POER
- Termostat Technoline
- Termostat Magnum
- Termostat Cotech
- Termostat Hornbach
Nyeste Termostat Manualer
27 Oktober 2024
27 Oktober 2024
27 Oktober 2024
27 Oktober 2024
27 Oktober 2024
27 Oktober 2024
27 Oktober 2024
27 Oktober 2024
27 Oktober 2024
27 Oktober 2024