INSTALLATION & WALK TEST
Installation
1. Open the cover by loosening the screw. Bend the clip
and remove the PCB module.
2. Route the cable into the unit base and mount the base
on the ceiling.
3. Replace the PCB module. Connect the cable to the
corresponding terminals according to the following
instructions.
Wiring Diagram
NC-COM-NO: Output for ON-OFF control of fan
coil operation.
24 V: Power supply (non-polarity)
4. Replace the front cover and perform the walk
test.
DESCRIPTION
GENERAL
The SA200-001 is a ceiling mount 360° occupancy sensor
designed for automatic HVAC system control. This sensor
provides a changeover (form C) output for fan coil controller
to activate/deactivate the operation of fan coil automatically.
Apply power, allowing 25 seconds for sensor to warm up.
The LED will blink (long and short) during warm up period.
Ensure the jumper head connectors of ON & OFF delays
are placed at “A” position (shortest delay). After the warm
up expires, walk across the (invisible) detection zones at
normal pace. The LED will light whenever sensor detects
the motion. Note: The LED will blink if any jumper connector
is not properly placed.
Walk Test
© Copyright 2004 PECO, Inc. All Rights Reserved P/N 68736 3220-1384 Rev1 Page 1
Installation Instructions
SA200-001
HVAC Occupancy Sensor
OPERATION
Operation Diagram
A. Standby
After warm up period expires, the
sensor enters into standby mode.
Sensor will check if delay jumpers
are properly placed. If not, the LED
will flash.
B. Relay ON Delay
Relay ON delay is the time given
to sensor to verify true occupancy
before activating the relay output.
Any further detection during ON
delay will NOT reset the timer.
C. 1-minute Waiting
When Relay ON delay expires, the
sensor enters into a 1-minute
waiting time. If no detection within
1 minute, then sensor will return
to standby mode. If any detection
occurs, then relay output will be
activated and Relay OFF delay will
be started.
A. Relay OFF Delay
Relay OFF delay is the time of
relay activating. Every detection
during this period will reset the
timer.
ON / OFF DELAY
The ON and OFF delays are designed to provide intelligent energy
management of HVAC system. ON delay is the time given to the
sensor to certify the occupancy, before it activates the fan
controller. OFF delay is the time that relay is active. Both ON and
OFF delays can be easily set by placing the jumper on the
corresponding pins as follows:
DETECTION PATTERN
A.
Standby
B.
Relay ON
Delay
C.
1-Minute
Waiting
D.
Relay OFF
Delay
(Relay Output)
A B C D E F
ON 0 sec. 10 sec. 30 sec. 1 min. 5 min. 10 min.
OFF 10 sec. 1 min. 5 min. 10 min. 20 min. 30 min.
READ THESE INSTRUCTIONS CAREFULLY BEFORE
ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS
DEVICE.
Failure to observe safety information and comply with
instructions could result in PERSONAL INJURY, DEATH AND/
OR PROPERTY DAMAGE.
To avoid electrical shock or damage to equipment, disconnect
power before installing or servicing.
To avoid potential fire and/ or explosion do not use in
potentially flammable or explosive atmospheres.
Retain these instructions for future reference. This product,
when installed, will be part of an engineered system whose
specifications and performance characteristics are not
designed or controlled by PECO, Inc. You must review your
application and national and local codes to assure that your
installation will be functional and safe.
WARNING
Use Copper wire only, insulate or wire nut
all un-used leads.
CAUTION
No
detection
Detection
Detection
© Copyright 2004 PECO, Inc. All Rights Reserved P/N 68736 3220-1385 Rev1 Page 2
Infrared sensor ................. Dual element
Power supply .................... 24 ± 2 V AC/DC
Detection range ................ Height x 2.5 at 25°C
Output format ................... Form C, 30 VDC, 0.2A max.
Current drain .................... 5 mA @24 VAC
Mounting height ............... 2.4~4.2 m
Detectable speed ............. 0.1~3.0 m/sec.
RFI immunity ................... Av. 20 V/m (10~1,000 MHz)
Temperature ..................... -20°C~38°C (-4°F ~ 100°F)
Humidity ........................... 95% RH max.
Dimensions ...................... 110 (Dia.) x 44 (H) mm
SPECIFICATIONS
Top View 360°
Side View