ENG CHANNEL8N 01 V00 03/17
CHANNEL8N
8 CHANNEL PT-100 SCANNER
96 x 96 DIN 1/4
96 mm / 3.78 inch
96 mm / 3.78 inch
12 ± 1 mm / 0.47 inch 84 mm / 3.31 inch
15 0.59 inchmm /
92mm/3.62 inch
92mm/3.62 inch
129mm/5.08 inch(min)
129mm/5.08 inch(min)
320 x 240 Pixel
TFT LCD
Standart
Function
Buttons
MENU BUTTON
Used to access Menu page.
ENTER BUTTON
Used to go in to selected page, to make parameter's cell
available to change and to confirm parameter’s change.
AUTO BUTTON
Used to auto-scan pages.
BACK BUTTON
Used to go back to previous menu and to cancel
parameter's change.
UP BUTTON
Used to go up in menus and lists and also used to increase
parameter's value.
LEFT BUTTON
Used to go left in menus.
F1 F2 F3 F4
F4F1 F2 F3
DOWN BUTTON
Used to go downin menus and lists and also used to
decrease parameter's value.
RIGHT BUTTON
Used to go right in menus.
F4
1F F2 3F
DELETE BUTTON
Used to erase logs on the screen.
SETTINGS
LOGS
ADVANCE
SETTINGS
LANGUAGE
CHANNEL8N 8 Channel PT-100 Scanner
- 320 x 240 pixel TFT LCD display
- 8 PT-100 temperature sensor inputs
- ON-OFF control
- Relay or (pnp “source”) transistor output
- Sensor error detection
- Adjustable temperature offset
- 3 Different alarm and pre-alarm types for each channel
(High, Low and Band Alarms)
- User defined channel labels
- Display scan modes
- Operating with Real Time Clock (RTC)
- ModBus RTU communication protocol
(RS-232, RS-485 and Ethernet communication)
- Data Logging to USB Flash Memory
- Adjustable data logging time interval
- Password protection for programming mode
CHANNEL8N series 8 channel PT100 scanner devices are designed for
measuring and logging temperature. They can be used in many
applications with their PT-100 process input, alarm outputs, selectable
alarm functions, RS-232 / RS-485 / Ethernet / USB communications.
SPECIFICATIONS
INPUT
Thermoresistance(RTD) : 2 wire PT100 (IEC 751) (ITS90)
Measurement Range : -200°C / +650°C
Accuracy : ± 0.25% of full scale
Sensor Break Protection : Upscale
W
OUTPUT
Relay :
ax. 1A@24V
DISPLAY
LCD Display : 320x240
POWER SUPPLY
ENVIRONMENTAL RATINGS
Operating Temperature : 0...50°C
Humidity : 0-90%RH (none condensing)
Protection Class : IP65 at front, IP20 at rear
PHYSICAL SPECIFICATIONS
Weight : 400 gr.
Dimension : 96 x 96 mm, Depth:96 mm
Panel Cut-Out : 92 x 92 mm
Sampling Time : 400msecs.
Line Compensation : Maximum 10
Input Ressistance : > 10MW
Resistive Load 5A@250V
(Electrical Life : 100.000 operation (Full Load)
Transistor : PNP(source) type transistor output (M )
pixel TFT LCD
100 - 240 V (-%15 / +%10) 50/60 Hz. 7VA
24 V (-%15 / +%10) 50/60 Hz. 7VA
24 V (-%15 / +%10) 7W
(It must be determined in order.)
Electrical Wiring Diagram
Device with Relay Outputs
RS 232
COMMUNICATION
5 x 5A@250V
COMMON-1
COMMON-2
16 21 22 23 24 25 26 27 28 29 3017 18 19 20
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
CH-1 ALARM
OUTPUT
CH-2 ALARM
OUTPUT
CH-3 ALARM
OUTPUT
CH-4 ALARM
OUTPUT
CH-5 ALARM
OUTPUT
CH-6 ALARM
OUTPUT
CH-7 ALARM
OUTPUT
CH-8 ALARM
OUTPUT
GENERAL ALR.
OUTPUT
GENERAL PRE-ALR.
OUTPUT
5 x 5A@250V
USB 2.0
COMMUNICATION
ETHERNET
OR
RS485
COMMUNICATION
PT-100
CH-1
PT-100
PT-100
PT-100
PT-100
PT-100
PT-100
PT-100
CH-2CH-3CH-4CH-5CH-6CH-7CH-8
AGND
100...240V - %15;+%10) 50/60Hz 7VA
24V (-%15;+%10) 50/60Hz 7VA
24V (-%15;+%10) 7W
L
(+)
N
(-)
Device with Transistor Outputs
RS 232
COMMUNICATION
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
USB 2.0
COMMUNICATION
ETHERNET
OR
RS485
COMMUNICATION
PT-100
CH-1
PT-100
PT-100
PT-100
PT-100
PT-100
PT-100
PT-100
CH-2CH-3CH-4CH-5CH-6CH-7CH-8
AGND
100...240V (- %15;+%10) 50/60Hz 7VA
24V (-%15;+%10) 50/60Hz 7VA
24V (-%15;+%10) 7W
L
(+)
N
(-)
i
i
i
i
iRS485, Ethernet and USB communications are optional
16 21 22 23 24 25 26 27 28 29 3017 18 19 20
CH-1 ALARM
OUTPUT
CH-2 ALARM
OUTPUT
CH-3 ALARM
OUTPUT
CH-4 ALARM
OUTPUT
CH-5 ALARM
OUTPUT
CH-6 ALARM
OUTPUT
CH-7 ALARM
OUTPUT
CH-8 ALARM
OUTPUT
GENERAL ALR.
OUTPUT
GENEAL PRE- ALR.
OUTPUT
10 x 1A@24V
TRANSISTOR OUTPUTS
POWER SUPPLY
24V ±%15
i
i
i
i
iRS485, Ethernet and USB communications are optional
Relay Outputs
(Alarm Outputs for
Channels 6 to 8,
General Alarm Output and
General Pre-Alarm Output )
CH = CHANNEL
Power Supply Input
(It must be determined in order.)
Process Inputs
(PT-100)
Common1 Common2
Relay Outputs
(Alarm Outputs for
Channels 1 to 5)
Power Supply Input
(It must be determined in order.)
Process Inputs
(PT-100)
Transistor Outputs
(Alarm Outputs for
Channels 1 to 8,
General Alarm Output and
General Pre-Alarm Output )
CH = CHANNEL
Maximum
CHANNEL8N Front View and Dimensions of
Panel Cut-Out
1-Before mounting the device
in your panel, make sure that
the cut-out is of the right size.
2-Check front panel gasket
position
3-Insert the device through the
cut-out. If the mounting clamps
are on the unit, put out them
before inserting the unit to the
panel.
Panel Mounting
Installation Fixing Clamp
The unit is designed for panel
mounting.
1-Insert the unit in the panel
cut-out from the front side.
2- Insert the mounting clamps
to the holes that located top
and bottom sides of device and
screw up the fixing screws until
the unit completely immobile
within the panel.
1
2
3
F1 F2 F3 F4
1
2
F1 F2 F3 4F
Removing from the Panel
1-Loosen the screws.
2-Pull mounting clamps from
top and bottom fixing sockets.
3-Pull the unit through the
front side of the panel
Definition of Front Panel
3
1
2
F1 F2 F3 4
F
MAIN OPERATION SCREEN
MAIN OPERATION (CHANNEL-1 SCREEN)
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
MENU SCREEN
OPERATOR PARAMETERS
PASSWORD SCREEN
Press F1 or F2 direction buttons
to move to the Settings tab.
When the F1 menu button is pressed
while the main screen is on the page, the
menu page is displayed.
PARAMETERS
CHANGE
PARAMETERS
CHANGE
OPERATOR PARAMETERS
(CHANNEL-1 PARAMETERS)
Press F3 button. If password
is different from 0, password
screen opens.
Enter the password value using
the F1 and F2 buttons.
Confirm the characters one by
one by pressing F3 button.
Once you have confirmed the
last character, you will proceed
to the operator parameters
screen.
Press the F1 and F2 buttons to
highlight the channel and press the F3
button.
Select the relevant parameter
with the F1 and F2 buttons.
Press the F3 button to select
the parameter.
Use the F1 and F2 buttons to change
the value of the parameter.
Press the F3 button to save
the parameter value.
DEVICE SETTINGS
(Rs485 SETTINGS)
DEVICE SETTINGS
(USB SETTINGS)
DEVICE SETTINGS
(ETHERNET SETTINGS)
DEVICE SETTINGS
(DATE TIME SETTINGS)
With the F1 and F2 buttons you can
select and change the USB
parameters. Use the F3 button to
save.
With the F1 and F2 buttons you can
select and change the RS485
parameters. Use the F3 button to
save.
With the F1 and F2 buttons you can
select and change the ETHERNET
parameters. Use the F3 button to
save.
With the F3 button you can select the
Date and Time parameters and you
can change the value with the F1, F2
buttons.
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
Channel Number
Device Function
Buttons
Alarm Set
Alarm set value for selected channel is can be adjusted according to this parameter.
It can be adjust between -200 0
O O
C to +65 C.
Pre. Alarm Set
Pre- Alarm set value for selected channel is can be adjusted according to this
parameter. It can be adjust between -200 0
O O
C to +65 C.
i
i
i
i
i
F4F1 F2 F3
Channel Label
PreAlarm Status
Alarm Status
Channels Names
Process Value
F4F1 F2 F3
F4F1 F2 F3
Alarm Messages
Channel Output
Status
Channel Number
F4F1 F2 F3 F4F1 F2 F3
F4F1 F2 F3 F4F1 F2 F3
F4F1 F2 F3 F4F1 F2 F3
F4F1 F2 F3 F4F1 F2 F3
F4F1 F2 F3F4F1 F2 F3
F4F1 F2 F3 F4F1 F2 F3
F4F1 F2 F3 F4F1 F2 F3
F4F1 F2 F3
F1
F1 F2
F3
F1
F2
F3
F1
F2
F1
F2 F3
F1
F2
Operator Password Change
Password for device is adjusted by this parameter.Operator
DEVICE SETTINGS
(PASSWORD CHANGE)
Use the F1 and F2 buttons to change
the value of the parameter. Confirm the
characters one by one by pressing F3
button.
Use the F1 button to move to
the "YES" tab and press the F3
button. In 1-3 seconds the
device will return to factory
settings.
F4F1 F2 F3 F4F1 F2 F3
TECHNICIAN PARAMETERS
(CONTROL PARAMETERS
TECHNICIAN PARAMETERS
PASSWORD SCREEN
TECHNICIAN PARAMETERS
PASSWORD SCREEN
TECHNICIAN PARAMETERS
PASSWORD INPUT SCREEN
Press F1 or F2 direction buttons
to move to the Advanced
Settings tab.
PARAMETERS
CHANGE
DEVICE SETTINGS
(RS232 SETTINGS)
Press F3 button. If password
is different from 0, password
screen opens.
Enter the password value using
the F1 and F2 buttons.
Confirm the characters one by
one by pressing F3 button.
Once you have confirmed the
last character, you will proceed
to the operator parameters
Use the F1 and F2 buttons to scroll to
the Control parameters and press the
F3 button.
Select the relevant channel with the F1
and F2 buttons.
Press the F3 button to select
the parameter.
Use the F1 and F2 buttons to change
the value of the parameter. Press the
F3 button to save the parameter value.
With the F1 and F2 buttons you
can select and change the RS232
parameters. Use the F3 button to
save.
F4F1 F2 F3 F4F1 F2 F3
F4F1 F2 F3 F4F1 F2 F3
F4F1 F2 F3 F4F1 F2 F3
F4F1 F2 F3 F4F1 F2 F3
F4F1 F2 F3F4F1 F2 F3
F1
F1 F2
F3
F1
F2
F3
F1
F2
F1
F2 F3
F3
F3
F3
F3
TECHNICIAN PARAMETERS
(CHANNEL-1)
TECHNICIAN PARAMETERS
(CHANNEL-1 PARAMETERS)
Main Operation Screens Definetion Accessing to the Operator Parameter Pages
If the display type parameter value Screen Type = MULTIPLE
If the display scan parameter value Screen Change = ENABLE, each main
operation screen is showing on LCD screen during time defined by Change
Time parameter value.
If the display type parameter value Screen Type = SINGLE
Channel Name
Process Value
MAIN OPERATION (CHANNEL-4 SCREEN)
Press number
F2 or F3
buttons for
accessing the
relevant channel
screen.
If the display scan parameter value Screen Change = ENABLE, each main
operation screen is showing on LCD screen during time defined by Change
Time(sec) parameter value
If more than one alarm messages is present, each alarm message is
showing on LCD screen during 1 second.
MAIN OPERATION SCREEN
OPERATOR PARAMETERS
PASSWORD SCREEN
OPERATOR PARAMETERS
PASSWORD INPUT SCREEN
OPERATOR PARAMETERS
(CHANNEL-1)
OPERATOR PARAMETERS
(CHANNEL-1 PARAMETERS)
Accessing to the Technician Parameter Pages
Operator Pages Parameters Definetions
If no operation is performed for 20 seconds in operator parameters section,
device turns to main operation screen automatically.
If the device has a optional RS485 communication then RS 485 page is
observed, If the device has a optional USB communication then USB page is
observed.
If no operation is performed for 20 seconds in operator or technician
parameters section, device turns to main operation screen automatically.
If the device has a optional ETHERNET communication then ETHERNET
page is observed, otherwise this page is not observed.
MAIN OPERATION SCREEN MENU SCREEN
When the F1 menu button is pressed
while the main screen is on the page, the
menu page is displayed.
DEVICE SETTINGS
(DEFAULT SETTINGS)
Hysteresis
Hysteresis parameter value for Alarm and Pre-Alarm is can be adjusted by this
parameter. It can be adjust between -400 0
O O
C to +40 C.
Band Alarm
Bandwith for Band alarm is can be adjusted by this parameter value.
It can be adjust between -400 0
O O
C to +40 C.
Sensor Alarm
Sensor break alarm for selected channel is can be disable or enable by this parameter.
It can be adjust between 0 to 1. Parameter values;
0 = DISABLE
1 = ENABLE
Offset
Process offset value for selected channel is can be adjusted by this parameter.
It can be adjust between -50.0 0
O O
C to +50. C.
Control Parameters- Other Parameters
Screen Type
Main operation screen type is adjusted by this parameter.
It can be adjust between 0 to 1. Parameter values;
0 = MULTIPLE
1 = SINGLE
Screen Change
It can be adjust between 0 to 1. Parameter values;
0 = DISABLE
1 = ENABLE
Display channel scanner mode is adjusted by this parameter.
Change Time(sec)
Display scan period is adjusted by this parameter. All main operation screen is
displayed during time defined by this parameter. It can be adjust between 1 to 3600
secs.
Baudrate
It can be adjust between 0 to 5. Parameter values;
0 = 4800
1 = 9600
2 = 19200
3 = 38400
4 = 57600
5 = 115200
Modbus communication baudrate for RS232 is can be adjusted by this parameter.
Parity
It can be adjust between 0 to 2. Parameter values;
0 = NONE
1 = ODD
2 = EVEN
Modbus communication parity bit for RS232 is can be adjusted by this parameter.
Stop Bit
It can be adjust between 1 to 2. Parameter values;
1 = 1 Stop bit
2 = 2 Stop bits
Modbus communication stop bit for RS232 is can be adjusted by this parameter.
Id
Modbus communication device ID for RS232 is can be adjusted by this parameter.
This parameter value is can be adjusted from 1 to 247.
File Name
USB file name for recording analogue values is can be adjusted by this parameter. File
name can be adjusted maximum 10 characters. Recording file on usb is “csv” format
and all data is seperated each other with tab. Example file format is explained below.
Label
When the analogue values are recorded on USB file, user can be defined label for this
recording. Label can be adjusted maximum 10 characters. Label are recorded at the
end of every lines of file.
Date Record
It can be adjust between 0 to 1. Parameter values;
0 = DISABLE
1 = ENABLE
When the analogue values are recorded on USB file, user can be save the recording
time on the file. Recording time is recorded at the beginning of every lines of file.
Record Time(sec)
It can be adjust between 0 to 3600 secs.
Record time interval is can be adjusted by this parameter. Analogue values are
recorded on USB file with this time interval. If
this parameter value is 0 usb recording is disabled.
Flash Memory “USB Flash Memory Stick Detected Test”
Detection of the USB memory device being inserted is tested with this parameter.
When the USB memory device is plugged in, the message "OK" is displayed.
DHCP
It can be adjust between 0 to 1. Parameter Values;
0 = DHCP DISABLE
1 = DHCP ENABLE
DHCP is an automatic configuration protocol used on IP networks, If DHCP is enable,
device is adjust our ethernet communication configuration parameters (IP,
Netmask,Gateway) dynamicaly for your network system. If DHCP is disable, you must
adjust ethernet configuration parameters (IP, Netmask,Gateway) for your network
system.
Port No
Ethernet port number is can be adjusted by this parameter.
Netmask
Subnet mask for ethernet communication is can be adjusted by this parameter. If
DHCP is selected as a enable there is no need to adjust to this parameter, if DHCP is
selected as a disable then user must adjust this parameter according to the their own
network system.
Gateway
Gateway for ethernet communication is can be adjusted by this parameter. If DHCP is
selected as a enable there is no need to adjust to this parameter, if DHCP is selected as
a disable then user must adjust this parameter according to the their own network
system.
Ip No
IP address for ethernet communication is can be adjusted by this parameter. If DHCP
is selected as a enable there is no need to adjust to this parameter, if DHCP is selected
as a disable then user must adjust this parameter.
Channel Status
It can be adjust between 0 to 1. If parameter value
0 = DISABLE
1 = ENABLE
Channel is enabled and disabled by this parameter. If channel is selected as a disabled
this channel is can not be observed in main operation scren for single view mode,
channel alarm is not be controlled and analogue value for this channel is can not be
recording on USB file. ,
Channel Name “ ” Channels label definition
All channels have their own label, is displayed in main operation screen. channel labels is can
be adjusted by this parameter. Channel labels are can be adjusted maximum 10 characters.
Alarm Type
Alarm type for selected channel is can be adjusted according to this parameter.
It can be adjust between 0 to 2. Parameter values;
0 = LOW
1 = HIGH
2 = BAND
PreAlarm Type
Pre-Alarm type for selected channel is can be adjusted according to this parameter.
It can be adjust between 0 to 2. Parameter values;
0 = LOW
1 = HIGH
2 = BAND
BackLightOnLevel
Display backlight is can be controlled by this parameter value. It can be adjust
between 50 to 100.
BackLightOffLevel
CO mode for backlight; in case off selection no backlight . ThisE parameter is can be
adjusted from 1 to 100.
BackLightOffTime
Time for the access to ecomomic backlight mode. This parameter is can be adjusted
from 10 to 300.
Device Settings - RS-232 Settings
Device Settings - RS-485 Settings
Baudrate
It can be adjust between 0 to 5. Parameter values;
0 = 4800
1 = 9600
2 = 19200
3 = 38400
4 = 57600
5 = 115200
Modbus communication baudrate for RS485 is can be adjusted by this parameter.
Parity
It can be adjust between 0 to 2. Parameter values;
0 = NONE
1 = ODD
2 = EVEN
Modbus communication parity bit for Rs485 is can be adjusted by this parameter.
Stop Bit
It can be adjust between 1 to 2. Parameter values;
1 = 1 Stop bit
2 = 2 Stop bits
Modbus communication stop bit for Rs485 is can be adjusted by this parameter.
Id
Modbus communication device ID for Rs485 is can be adjusted by this parameter.
This parameter value is can be adjusted from 1 to 247.
Device Settings - USB Settings
Device Settings - ETHERNET Settings
TcpIp Selection
It can be adjust between 0 to 1.
0 = Modbus RTU Over TCP/IP
1 = Modbus RTU TCP/IP
TCP/IP Protocol is can be adjusted by this parameter.
Device Settings -Default Settings
This section is used to return default settings back.
Device Settings - Date and Time Settings
Date and Time for device is adjusted by this parameter.
Device Settings - Password Change
Technician Password for device is adjusted by this parameter.
Device Settings - Software Update
It allows you to update the device's software with a USB flash memory.
Logs
In this page, events logs are shown.
Language Selection
In this page, the language is selected for the device.
F4F1 F2 F3
F4F1 F2 F3
SET = Alarm or Pre-Alarm Set value
HYS = Hysteresis value for Alarm and Pre-Alarm output
BAND= Bandwidth for Band Alarm.
ON
OFF
Process Value
ON
OFF
Alarm
Output
Process Value
Alarm
Output
SET
HYS
SET
HYS
ON
OFF
Alarm
Output
Process Value
Band Alarm
Low Alarm
High Alarm
Operation Graphics of Alarm and Pre-Alarm Types
i
i
i
i
i
Modbus Addresses
Output Status Addresses
Outputs Status Addresses Unit
CH-1 ALARM OUT Channel-1 Alarm Output Status
Address
00001
-
CH-2 ALARM OUT Channel-2 Alarm Output Status 00002
-
CH-3 ALARM OUT Channel-3 Alarm Output Status 00003
-
CH-4 ALARM OUT Channel-4 Alarm Output Status 00004
-
CH-5 ALARM OUT Channel-5 Alarm Output Status 00005
-
CH-6 ALARM OUT Channel-6 Alarm Output Status 00006
-
CH-7 ALARM OUT Channel-7 Alarm Output Status 00007
-
CH-8 ALARM OUT Channel-8 Alarm Output Status 00008
-
GEN. ALR. OUT General Alarm Output Status 00009
-
GEN.PRE.ALR. OUT General Pre-alarm Output Status 00010
-
Note-1: Outputs status are can be readed with modbus function-1 (read coils).
Device’s response for modbus function-1 is always 2 byte data although the modbus
function request less than 9 outputs port.
Process Values Addresses
Process Values Addresses Unit
CH-1 P. VALUE Channel-1 Process Value
Address
30001
OC
CH-2 P. VALUE Channel-2 Process Value 30002
CH-3 P. VALUE Channel-3 Process Value 30003
CH-4 P. VALUE Channel-4 Process Value 30004
CH-5 P. VALUE Channel-5 Process Value 30005
CH-6 P. VALUE Channel-6 Process Value 30006
CH-7 P. VALUE Channel-7 Process Value 30007
CH-8 P. VALUE Channel-8 Process Value 30008
Note-2: Process values are can be readed with modbus function-4 (read input
register). Because of the process values are displayed on LCD screen with point, the
reading values from modbus is 10 times than the real values.
OC
OC
OC
OC
OC
OC
OC
Parameters Modbus Addresses
Parameter Values Addresses Unit
CH-1 NAME Channel-1 Name
Address
42000 - 42004
CH-2 NAME Channel-2 Name 42005 - 42009String 42005 - 42009
CH-3 NAME Channel-3 Name 42010 - 42014
CH-4 NAME Channel-4 Name 42015 - 42019
CH-5 NAME Channel-5 Name 42020 - 42024
CH-6 NAME Channel-6 Name 42025 - 42029
CH-7 NAME Channel-7 Name 42030 - 42034
CH-8 NAME Channel-8 Name 42035 - 42039
String
String
String
String
String
String
String
FILE NAME USB File Name 42040 - 42044String
LABEL USB Label 42045 - 42049String
CH-1 ALARM SET Channel-1 Alarm Set Value 42050
CH-1 PRE A. SET Channel-1 Prealarm Set Value 42051
CH-1 HYSTERESIS Channel-1 Hysteresis Value 42052
CH-1 BAND ALARM Channel-1 Bandwith Value 42053
CH-2 ALARM SET Channel-2 Alarm Set Value 42054
CH-2 PRE A. SET Channel-2 Prealarm Set Value 42055
CH-2 HYSTERESIS Channel-2 Hysteresis Value 42056
CH-2 BAND ALARM Channel-2 Bandwith Value 42057
CH-3 ALARM SET Channel-3 Alarm Set Value 42058
CH-3 PRE A. SET Channel-3 Prealarm Set Value 42059
CH-3 HYSTERESIS Channel-3 Hysteresis Value 42060
CH-3 BAND ALARM Channel-3 Bandwith Value 42061
CH-4 ALARM SET Channel-4 Alarm Set Value 42062
CH-4 PRE A. SET Channel-4 Prealarm Set Value 42063
CH-4 HYSTERESIS Channel-4 Hysteresis Value 42064
CH-4 BAND ALARM Channel-4 Bandwith Value 42065
CH-5 ALARM SET Channel-5 Alarm Set Value 42066
CH-5 PRE A. SET Channel-5 Prealarm Set Value 42067
CH-5 HYSTERESIS Channel-5 Hysteresis Value 42068
CH-5 BAND ALARM Channel-5 Bandwith Value 42069
CH-6 ALARM SET Channel-6 Alarm Set Value 42070
CH-6 PRE A. SET Channel-6 Prealarm Set Value 42071
CH-6 HYSTERESIS Channel-6 Hysteresis Value 42072
CH-6 BAND ALARM Channel-6 Bandwith Value 42073
CH-7 ALARM SET Channel-7 Alarm Set Value 42074
CH-7 PRE A. SET Channel-7 Prealarm Set Value 42075
CH-7 HYSTERESIS Channel-7 Hysteresis Value 42076
CH-7 BAND ALARM Channel-7 Bandwith Value 42077
OC
OC
OC
OC
OC
OC
OC
OC
OC
OC
OC
OC
OC
OC
OC
OC
OC
OC
OC
OC
OC
OC
OC
OC
OC
OC
OC
OC
*
( )
*
( )
*
( )
*
( )
*
( )
*
( )
*
( )
*
( )
*
( )
*
( )
*
( )
*
( )
*
( )
*
( )
*
( )
*
( )
*
( )
*
( )
*
( )
*
( )
*
( )
*
( )
*
( )
*
( )
*
( )
*
( )
*
( )
*
( )
SET
(SET - (BAND/2)) (SET + (BAND/2))
HYS HYS
Technician Parameters
Technician Pages Parameters Definetions
USB Recording File Example
2011-06-23-17:26:09 130.6 129.1 130.5 129.5 130.0 129.9 130.3 129.1 SAMPLE
2011-06-23-17:26:10 130.6 129.1 130.5 129.5 130.0 129.9 130.3 129.1 SAMPLE
2011-06-23-17:26:12 130.6 129.1 130.5 129.5 130.0 129.9 130.3 129.1 SAMPLE
2011-06-23-17:26:13 130.6 129.1 130.5 129.5 130.0 129.9 130.3 129.1 SAMPLE
Recording Time CH-1
Value
CH-2
Value
CH-3
Value
CH-4
Value
CH-5
Value
CH-6
Value
CH-7
Value
CH-8
Value
Label
Internal Recording
The device can record in memory. When a USB memory is inserted, the recordings are
transferred to the USB memory with the file name containing the current date and
time.(Exp: 2017-07-30-09-08-12-CHAN8.txt) icon and transaction status (%)
are displayed on the screen until the transfer is complete.
If you want to eject the USB memory during transfer or recording; Press the F4 button
for 5 seconds and the USB memory must be removed (within 5 seconds) before the
icon on the screen disappears. If the USB stick is not removed during this time, the
transfer will resume from where it left off.
Not: The device can store up to (Record time x 2) daily memos in its memory.
Produkspesifikasjoner
Merke: | Emko |
Kategori: | Termostat |
Modell: | CHANNEL8N |
Trenger du hjelp?
Hvis du trenger hjelp med Emko CHANNEL8N still et spørsmål nedenfor, og andre brukere vil svare deg
Termostat Emko Manualer
27 Oktober 2024
27 Oktober 2024
27 Oktober 2024
27 Oktober 2024
27 Oktober 2024
27 Oktober 2024
22 Oktober 2024
Termostat Manualer
- Termostat ORNO
- Termostat Bosch
- Termostat Boneco
- Termostat Siemens
- Termostat EBERLE
- Termostat Schwaiger
- Termostat AEG
- Termostat TP Link
- Termostat Oreg
- Termostat Netatmo
- Termostat Busch-Jaeger
- Termostat Brennenstuhl
- Termostat Danfoss
- Termostat Somfy
- Termostat Panasonic
- Termostat Schneider
- Termostat EMOS
- Termostat Heatit
- Termostat Dimplex
- Termostat Velleman
- Termostat GE
- Termostat Nexa
- Termostat Nobo
- Termostat Tru Components
- Termostat Bearware
- Termostat Elgato
- Termostat Avidsen
- Termostat STI
- Termostat Hunter
- Termostat Basetech
- Termostat TFA
- Termostat Tesla
- Termostat Renkforce
- Termostat REMKO
- Termostat ATAG
- Termostat Drayton
- Termostat Jung
- Termostat Ambiano
- Termostat Crestron
- Termostat Xavax
- Termostat Techno Line
- Termostat Remeha
- Termostat Heatmiser
- Termostat Wolf
- Termostat GENERAL Life
- Termostat Silvercrest
- Termostat AVM
- Termostat HomePilot
- Termostat Elektrobock
- Termostat Corberó
- Termostat Perel
- Termostat Delta Dore
- Termostat Homematic IP
- Termostat Vimar
- Termostat Emerson
- Termostat Salus
- Termostat Fenix
- Termostat Honeywell
- Termostat Junkers
- Termostat Eliwell
- Termostat Grasslin
- Termostat Jumo
- Termostat Enda
- Termostat Orbis
- Termostat Fantini Cosmi
- Termostat Vemer
- Termostat Qubino
- Termostat Theben
- Termostat EQ3
- Termostat Etherma
- Termostat Saunier Duval
- Termostat Gewiss
- Termostat Viessmann
- Termostat Bticino
- Termostat Conrad
- Termostat Econo-Heat
- Termostat Elro
- Termostat Gira
- Termostat Tado
- Termostat Brink
- Termostat Emmeti
- Termostat Itho
- Termostat Bryant
- Termostat Aube
- Termostat Baxi
- Termostat Seitron
- Termostat Amfra
- Termostat Vaillant
- Termostat Carel
- Termostat Buderus
- Termostat Optima
- Termostat Frico
- Termostat UPM
- Termostat Computherm
- Termostat Veria
- Termostat Innogy
- Termostat Nefit
- Termostat ICY
- Termostat Levica
- Termostat Itho-Daalderop
- Termostat Carrier
- Termostat Radson
- Termostat ChiliTec
- Termostat King
- Termostat ACV
- Termostat Landis Gyr
- Termostat Nest
- Termostat Oventrop
- Termostat IMIT
- Termostat Horstmann
- Termostat ELKO
- Termostat Alecto
- Termostat Google
- Termostat Wachendorff
- Termostat MundoControl
- Termostat Otio
- Termostat Rose LM
- Termostat Tylö
- Termostat Sinustec
- Termostat TrickleStar
- Termostat Finder
- Termostat Sygonix
- Termostat Warmup
- Termostat Plugwise
- Termostat Lowes
- Termostat Go Green
- Termostat Drayton Erie
- Termostat Intertechno
- Termostat EQ-3
- Termostat Johnson Control
- Termostat RWE
- Termostat Webasto
- Termostat Tellur
- Termostat OJ ELECTRONICS
- Termostat Zehnder
- Termostat Plieger
- Termostat HomeMatic
- Termostat Eneco
- Termostat VDH
- Termostat Maico
- Termostat Yokis
- Termostat Eurotronic
- Termostat HQ
- Termostat Ouellet
- Termostat THERMAFLEX
- Termostat Truma
- Termostat Wallair
- Termostat AWB
- Termostat PECO
- Termostat Worcester-Bosch
- Termostat 2Heat
- Termostat EasyTemp
- Termostat Hugo Muller
- Termostat Watts
- Termostat Westfalia
- Termostat Oregon Scientific
- Termostat H-Tronic
- Termostat Z-Wave
- Termostat Easy Timer
- Termostat Fibaro
- Termostat SPC
- Termostat Muller
- Termostat Bulex
- Termostat Helios (Amfra)
- Termostat IR-V
- Termostat Eqiva
- Termostat Hager
- Termostat Energenie
- Termostat Thermy
- Termostat Ferroli
- Termostat Niko
- Termostat Stiebel Eltron
- Termostat De Dietrich
- Termostat POER
- Termostat Technoline
- Termostat Magnum
- Termostat Cotech
- Termostat Hornbach
Nyeste Termostat Manualer
27 Oktober 2024
27 Oktober 2024
27 Oktober 2024
27 Oktober 2024
27 Oktober 2024
27 Oktober 2024
27 Oktober 2024
27 Oktober 2024
27 Oktober 2024
27 Oktober 2024